Programming

5-17

Advanced Setup Group

(continued)

[Break Voltage]

Sets the voltage the drive will output at [Break Frequency].
Combined with [Break Frequency], this value determines the
Volts-per-Hz ratio between 0 and [Break Frequency].

Parameter #

Parameter Type

50

Read & Write

Factory Default

Minimum

115V for 230V Drive
230V for 460V Drive

0 Volts

Volts-per-Hz ratio between 0 and [Break Frequency].

Important: [DC Boost Select] must be set to ‘‘Break
Point” to activate this parameter.

Units 1 Volt

Maximum 50% of Max. Drive Rated Volts

[Maximum Voltage]

Parameter # 20

Factory Default Max. Drive Rated Volts

[Maximum Voltage]

Parameter Type Read & Write

Minimum 25% of Max. Drive Rated Volts

Sets the highest voltage the drive will output.

Important: [Maximum Voltage] does not have to be set
greater than [Base Voltage], but the maximum drive output
is limited to [Maximum Voltage].

Units 1 Volt

Maximum 110% of Max. Drive Rated Volts

[Base Voltage]
[Base Frequency]

Maximum

'

a

[Maximum Voltage]

[Maximum Frequency]

b

y

Motor Rated

Maximum

0

0

Voltage

Frequency

b

[Break Voltage]
[Break Frequency]

Start Boost

'

y

Motor Rated

'

Figure 5.7 Custom Volts-per-Hz Pattern

This pattern is active only when [DC Boost Select] is set
to ‘‘Break Point.”

The following guidelines should be followed when setting up
a custom Volts-per-Hz curve:

1.

[Base Voltage] must be greater than [Start Boost].

2.

If [DC Boost Select] is set to “Break Point” then:

[Base Voltage] must be greater than [Break Voltage] and
[Break Voltage] must be greater than [Start Boost].