Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 122

Advertising
background image

Programming

5-54

This group contains the parameters needed for an optional communications adapter to communicate with the
drive.

Adapter

I/O

[Data In A1 through D2]

Parameter # 111 - 118

[Data In A1 through D2]

Parameter Type Read & Write

These parameters are used to write real time data values
from a source controller (PLC, SLC, etc.) to the drive. This
is accomplished by programming a parameter number into
the [Data In] parameters. The value programmed into the
source controller’s output image table will be written to the
drive parameter identified in the corresponding [Data In]
parameter.

Bulletin 1305 drive

Controller Output Image Table (i.e. PLC, SLC, etc.)

Important: addressing information that defines which controller I/O
address corresponds to a [Data In] parameter is determined by the
dip switch settings on the external communication module. Refer to
the appropriate Bulletin 1203 Communication Module User Manual
for details.

Refer to Appendix B for additional information.

Parameter
111

Data In A1

112

Data In A2

113

Data In B1

114

Data In B2

115

Data In C1

116

Data In C2

117

Data In D1

118

Data In D2

Important: The drive parameter that is accessed indirectly using Data In will not be stored permanently and automatically to
EEPROM (due to the high potential update rate from a PLC). A manual operation is necessary for permanent storage. The HIM
EEPROM command, Save Values, or using parameter (64) [Set Defaults] will perform this task. Similarly, to restore the values to
the ones the drive had before Data In was configured, the HIM Recall Values Function can be used.

[Data Out A1 through D2]

Parameter # 119 - 126

[Data Out A1 through D2]

Parameter Type Read & Write

These parameters are used to write real time data values
from the drive to a destination controller. This is
accomplished by programming a parameter number into
the [Data Out] parameters. The real time value of that
parameter will be written to the input image table of the
destination controller.

Bulletin 1305 drive

Controller Input Image Table (i.e. PLC, SLC, etc.)

Important: addressing information that defines which controller I/O
address corresponds to a [Data Out] parameter is determined by the
dip switch settings on the external communication module. Refer to
the appropriate Bulletin 1203 Communication Module User Manual
for details.
Refer to Appendix B for additional information.

119

Data Out A1

120

Data Out A2

121

Data Out B1

122

Data Out B2

123

Data Out C1

124

Data Out C2

125

Data Out D1

126

Data Out D2

Parameter

Advertising