Serial Communications

B-8

Table B.4 Parameter Grouping/User Settings

(continued)

Group Parameter Name

Parameter
Number

Display
Units

Drive Units
Scale Factor

Minimum

Maximum

Factory Setting

User’s
Setting

Freq Select 1

5

Text

1

––

––

Adapter 1

Freq Select 2

6

Text

1

––

–––

Remote Pot

Jog Frequency

24

Hz

100

0.0

400.0

10.0

Prst/2nd Accel

26

Text

1

––

––

Preset

Upper Presets

72

Text

1

––

––

Disabled

Accel Time 2

30

Seconds

10

0.0

3600.0

5.0

Decel Time 2

31

Seconds

10

0.0

3600.0

5.0

S

et

Preset Freq 1

27

Hz

100

0.0

400.0

10.0

cy

S

Preset Freq 2

28

Hz

100

0.0

400.0

20.0

u

enc

Preset Freq 3

29

Hz

100

0.0

400.0

30.0

equ

e

Preset Freq 4

73

Hz

100

0.0

400.0

40.0

Fre

q

Preset Freq 5

74

Hz

100

0.0

400.0

50.0

F

Preset Freq 6

75

Hz

100

0.0

400.0

60.0

Preset Freq 7

76

Hz

100

0.0

400.0

0.0

Skip Freq 1

32

Hz

1

0

400

400

Skip Freq 2

33

Hz

1

0

400

400

Skip Freq 3

34

Hz

1

0

400

400

Skip Freq Band

35

Hz

1

0

15

0

MOP Increment

22

Hz/Second

1

0.00

255.00

1.00

Analog Filter

144

Text

1

––

––

100%

Refer to Table B.7 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions.

Refer to page B-2.