Installation/Wiring

2-21

Figure Notes:

Required to operate drive. STOP also used to clear a fault.
Use HIM Stop button to clear faults.
Contact Closure Input. Internal 5V supply. DO NOT apply external voltage.
When the ENABLE signal is lost, the drive output immediately shuts off and the

motor will coast to a stop.

A Start command will override any Jog command.
See Table 5.C on Page 5-31 for more information.

The recommended control signal wire is:

D Belden 8760 (or equiv.) - 18 AWG (0.750 mm

2

), twisted

pair, shielded.

D Belden 8770 (or equiv.) - 18 AWG (0.750 mm

2

), 3

conductor, shielded.

D Belden 9460 (or equiv.) - 18 AWG (0.750 mm

2

), twisted

pair, shielded.

Important: Control inputs to two or more drives must NOT
be connected in parallel.

Table 2.F

Control Terminal Block (TB2) Descriptions

Terminal

Signal

Specification

1, 2, 3
2,3
4,3
5, 3
6, 7
8, 7
9, 10

11, 12
13, 12
14, 15
16, 15
17, 15
18, 15
19, 20

External Speed Pot
0-10V Analog Input
4-20mA Analog Input
0-10V Analog Output
Start
Stop
Programmable Output 1

Drive Enable
Reverse
Jog
SW1
SW2
SW3
Programmable Output 2

10 k

Ω Potentiometer, 2 Watts

Drive Input Impedance = 100 k

Drive Input Impedance = 250

Meter Impedance

≥ 4 kΩ

Contact Closure Input

Contact Closure Input

Resistive Rating = 115 V AC/30 VDC, 5A
Inductive Rating = 115 V AC/30 VDC, 2A
Contact Closure Input

➂➃

Contact Closure Input

Contact Closure Input

Contact Closure Input

Contact Closure Input

Contact Closure Input

24V DC

"20%, 50 mA Max. (Sink)

Recommended practice is to run all signal wiring in a separate
steel conduit. The shield wire must only be connected at the
drive.

ATTENTION: Signal common is internally
connected to chassis ground. Do not use cable
shields as signal current paths.

!