Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 78

Advertising
background image

Programming

5-10

Setup Group

(continued)

[Base Frequency]

Parameter # 17

Factory Default 60 Hz

[Base Frequency]

Parameter Type Read & Write

Minimum 40 Hz

This value should be set to the motor nameplate Rated
Frequency.

Units 1 Hz

Maximum 400 Hz

[Base Voltage]

Parameter # 18

Factory Default Max. Drive Rated Volts

[Base Voltage]

Parameter Type Read & Write

Minimum 25% of Max. Drive Rated Volts

This value should be set to the motor nameplate Rated
Voltage.

Units 1 Volt

Maximum 100% of Max. Drive Rated Volts

[Maximum Voltage]

Parameter # 20

Factory Default Max. Drive Rated Volts

[Maximum Voltage]

Parameter Type Read & Write

Minimum 25% of Max. Drive Rated Voltage

This parameter sets the highest voltage the drive will
output.

Units 1 Volt

Maximum 110% of Max. Drive Rated Volts

[Minimum Freq]

Parameter # 16

Factory Default 0 Hz

[Minimum Freq]

Parameter Type Read & Write

Minimum 0 Hz

This parameter sets the lowest frequency the drive will
output.

Important: All analog inputs to the drive (4-20mA, 0-10V,
Remote Pot) are scaled for the range [Minimum Freq] to
[Maximum Freq].

Units 1 Hz

Maximum 120 Hz

Important: This parameter can not be
programmed while the drive is running.