Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 148

Advertising
background image

Serial Communications

B-6

Table B.4 Parameter Grouping/User Settings

(continued)

Group Parameter Name

Parameter
Number

Display
Units

Drive Units
Scale Factor

Minimum

Maximum

Factory Setting

User‘s
Setting

Input Mode

21

Text

1

––

––

Three Wire

Freq Select 1

5

Text

1

––

––

Adapter 1

Accel Time 1

7

Seconds

10

0.0

3600.0

10.0

Decel Time 1

8

Seconds

10

0.0

3600.0

10.0

Base Frequency

17

Hz

1

40

400

60

Base Voltage

18

Volts

1

25% of DRV

100% of Drive Rated Volts

Drive Rated Volts

p

Maximum Voltage

20

Volts

1

25% of DRV

110% of Drive Rated Volts

Drive Rated Volts

t Up

Minimum Freq

16

Hz

1

0

120

0

S

et

U

Maximum Freq

19

Hz

1

40

400

60

S

Stop Select

10

Text

1

––

––

Ramp

Current Limit

36

%

1

20% of DRC

150% of Drive Rated Current (DRC)

150% of DRC

Overload Mode

37

Text

1

––

––

No Derating

Overload Current

38

Amps

100 = DRC

20% of DRC

115% of Drive Rated Current (DRC)

115% of DRC

Sec Curr Limit

141

%

1

0

% of DRC

150% of Drive Rated Current (DRC)

0

% of DRC

Adaptive I Lim

149

Text

1

––

––

Enabled

Refer to Table B.6 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions

Refer to page B-2.