2 - operation, Instrument configuration (set-up mode), Chapter 2 – Rockwell Automation 1412-PP21xx PowerPad Portable Powermonitor User Manual

Page 15: Operation, Chapter

Advertising
background image

Rockwell Automation Publication 1412-UM001D-EN-P - September 2012

15

Chapter

2

Operation

The instrument is turned ON by pressing the green power button. The startup

screen appears and indicates the instrument's software version and serial number.

If there is no AC power supply, the instrument operates on batteries. The

instrument's batteries are charged when it is connected to a 120/240; 60/50Hz

line.

The instrument is turned OFF by pressing the green power button. Power off

confirmation is asked if the instrument is recording or detecting transients.

Instrument Configuration

(Set-up Mode)

This product contains a sealed NiMH battery which is permanently connected and

should only be removed or replaced by trained professionals.
At the end of its life, the battery contained in this product should be collected
separately from any unsorted municipal waste.
The collection and recycling of batteries helps protect the environment and
contributes to the conservation of natural resources as valuable materials are
recovered.

TIP

The current probes connected are identified at power ON only. Restart the

PowerPad unit after the probe type is changed.

TIP

All configurations are available through the DATAVIEW software.

IMPORTANT

The instrument must be configured the first time it is used and then whenever

necessary, should your needs change. The configuration is saved in the non-
volatile memory when the instrument is turned OFF.