Harmonic analysis in expert mode – Rockwell Automation 1412-PP21xx PowerPad Portable Powermonitor User Manual

Page 34

Advertising
background image

34

Rockwell Automation Publication 1412-UM001D-EN-P - September 2012

Chapter 3

Display Modes

The signs are only available in harmonic power measurement.

The

Power and Direction Flow Analysis

example shows a power harmonic

display with the 3rd harmonic highlighted by the cursor. This harmonic is

generated by the load.

Harmonic Analysis in Expert Mode

Press the Up Cursor button to select -.+ and then either the V or A variable

function button V or A.

This is an example of a typical display.

First column: The harmonics inducing a negative sequence are displayed.
Second column: Those inducing a zero sequence (triplens added into the

neutral) are displayed.

Third column: Those inducing a positive sequence are displayed.

Harmonic contest is useful to evaluate the influence of harmonics causing heating

of the neutral or on rotating machines can be analyzed.

TIP

By convention, positive harmonics are from supply to load, and negative
harmonics are from load to supply.