Rockwell Automation 1412-PP21xx PowerPad Portable Powermonitor User Manual

Page 22

Advertising
background image

22

Rockwell Automation Publication 1412-UM001D-EN-P - September 2012

Chapter 2

Operation

Use the same process to select the upper limit.

6. Press the Right Cursor button again to move to the right and modify the

last value needed to complete the definition.
Here you will choose whether to include all harmonics or only the odd

harmonics.

7. Use the Up/Down Cursor buttons to make this selection.

The diamond preceding the Odd Only choice will appear filled in for

selected and unfilled for not selected.

8. Press the Enter button when you have finished selecting all the parameters

to be recorded to apply the new setup.

EXAMPLE

Example of a user defined choice:
Vh 02  15

Odd Only.

In this user defined condition, all odd voltage harmonics between the 2nd and
the 15th are recorded.

WARNING: The battery may fully discharge when recording for long

periods of time while not connected to a power supply. The PowerPad
unit will continue to record for some time, even if below the minimum
battery charge value. However, the display may not come back on, and

will eventually stop saving data when the battery is too low. All data
recorded will be saved.
If in the Record Mode, and the display does not come ON, do not turn the

instrument OFF. Supply power to the PowerPad unit with the line cord and
the display will come back ON when any button (other than ON/OFF) is
pressed.