Electrical hookup (electrical network) – Rockwell Automation 1412-PP21xx PowerPad Portable Powermonitor User Manual

Page 18

Advertising
background image

18

Rockwell Automation Publication 1412-UM001D-EN-P - September 2012

Chapter 2

Operation

Electrical Hookup (Electrical Network)

Follow these steps to select the type of power system the PowerPad unit will

measure.

1. Highlight ELECTRICAL HOOKUP with the Up/Down Cursor

buttons, then press Enter.
This screen appears.

2. Choose the hookup type with the Up/Down and Left/Right Cursor

buttons.

3. Press Enter to apply the new hookup selection.

The Configuration menu is once again displayed on the screen.

Hookup Types

These are the types of power systems the PowerPad unit can measure:

Single or two-phase: The neutral current is not measured or calculated.
Three-phase, three-wire connection (3V, 3 A):

On DELTA network: Only power totals are measured.

Powers per phase are displayed, but not valid.

On WYE network: The neutral current is not calculated. It is necessary

to connect neutral (V) to obtain the power per phase.

Three-phase, four-wire connection (4V, 3 A): The neutral current is

available and its value and waveform are displayed.
On WYE network: Powers per phase are available.

TIP

Neutral current is calculated, not measured, in the four-wire hookup.

ATTENTION: V1 must be connected in all hookups, since the display is
synchronized from V1 and the network frequency measured by V1.

N
L1

Single-phase

N
L1
L2

Two-phase

N
L1
L2
L3

3 phase-3 wire

(DELTA)

N
L1
L2
L3

3 phase-4 wire

(WYE)