Save the display – Rockwell Automation 1412-PP21xx PowerPad Portable Powermonitor User Manual

Page 47

Advertising
background image

Rockwell Automation Publication 1412-UM001D-EN-P - September 2012

47

Display Modes

Chapter 3

It is possible to make an energy measurement over several recording ranges in the

4 quadrants.

The Plus

and Minus

buttons allow the integration period of the

displayed measurement and the graph time-scale to be changed.

Save the Display

This button lets you save 12 snapshots for future recall and evaluation:

Press the Camera button (for about 3s) to capture a snapshot of the

current display.

The Camera icon is displayed in the top left corner as soon as the

operation is successful.

This icon is replaced by the Trash Can

if there is no space left in the

memory to record the display.

TIP

All data in a recording session can be downloaded to a computer by using the
DATAVIEW software.

Display Averaging Period

Graph Scale

2 hours

over 5 days

1 hour

over 2 1/2 days

15 minutes

over 15 hours

10 minutes

over 10 hours

5 minutes

over 5 hours

1 minute

over 1 hour

20 seconds

over 20 minutes

5 seconds

over 5 minutes

1 second

over 1 minute

TIP

The minimum integration period is limited by the recording period. The
recording integration period of two minutes is a special case. In this case, only

the following display integration periods are possible: 10 minutes, one hour,
and two hours.

TIP

These screens can be downloaded to a computer via the DATAVIEW software.