Mathematical Formulas For Various Parameters

Appendix C

Ratios

Various Types of Energy

Total active energy consumed:

Wh[0][3] = Wh[0][0] + Wh[0][1] + Wh[0][2]

Total apparent energy consumed:

VAh[0][3] = VAh[0][0] + VAh[0][1] + VAh[0][2]

Total reactive capacitive energy consumed:

VARhC[0][3] = VARhC[0][0] + VARhC[0][1] + VARhC[0][2]

Total reactive inductive energy consumed:

VARhL[0][3] = VARhL[0][0] + VARhL[0][1] + VARhL[0][2]

PF[i] =

i + 1 phase power factor

W[i]

VA[i]

DPF[i] = cos(

φ[i])

i + 1 phase displacement factor

Tan[i] = tan(

φ[i])

i + 1 phase tangent

PF[3] =

PF[0] + PF[1] + PF[2]

3

Total power factor

DPF[3] =

DPF[0] + DPF[1] + DPF[2]

3

Total shift factor

Tan[3] =

Tan[0] + Tan[1] + Tan[2]

3

Total tangent

cos(

φ[i]) =

[][ ]

Cosine angle between voltage
fundamental and i + 1 phase current

NSS-1

0

2

n

i

VF

[][ ]

n

i

AF

n

=

[][ ]

NSS-1

0

n

i

VF

n

=

2

[][ ]

NSS-1

0

n

i

AF

n

=

.

Wh[0][i] =

Active energy consumed phase i + 1

W[i]

3600

Tint

VAh[0][i] =

Apparent energy consumed phase i + 1

VA[i]

3600

Tint

VARhL[0][i] =

for VAR[i]

≥0

Reactive inductive energy consumed phase i + 1

VAR[i]

3600

Tint

VARhC[0][i] =

for VAR[i]

≤0

Reactive capacitive energy consumed phase i + 1

3600

Tint

– VAR[i]