Set alarm – Rockwell Automation 1412-PP21xx PowerPad Portable Powermonitor User Manual

Page 23

Advertising
background image

Rockwell Automation Publication 1412-UM001D-EN-P - September 2012

23

Operation

Chapter 2

Set Alarm

Follow these steps the set the alarms.

1. Highlight ALARM with the Up/Down Cursor buttons, then press Enter.

This screen appears.

ATTENTION: A programmed alarm must be set to ON to function properly
(general activation or deactivation of alarms is generated in the Alarm mode).
Modifying one or several characteristics of an alarm set to ON, automatically
switches it to OFF.

Hysteresis Percentage (1, 2, 5, or 10%)

Alarm activation (ON or OFF)

Alarm number (1…10)

There are 24 parameters to choose from for alarm triggering. They are: Vrms, Urms, Arms, Vpst, Vcf, Ucf, Acf,

Vumb, Aumb, Hz, Akf, Vthd, Uthd, Athd, W, VAR, VA, DPF, PF, Tan, Vh, Uh, Ah, and VAh.

Threshold value for triggering an alarm

Minimum duration from beginning threshold detection to store the alarm (from 0.01 s to 99 m)

Less than < or greater than >

Capture -

3L: capture all phases (1, 2, or 3 depending on hookup selection)

N: neutral capture

: total power capture

/3: average value of 3-phase capture (S/3 for 2-phase)

0…50 harmonic order available for harmonic event capture

07/25/02 10:26

100%

Hysteresis 10 %

ON

ON

ON

ON

ON

ON

ON

3L

3L

3L

3L
Σ
3L

3L

01 s

02 s

01 s

05 min

15 min

01 min

10 min

2 1 0 V

0 0 2 0 A

0 8.0 %

1 0.0 %

1 0 0 0 W

0.9 2

0 5.0 %

<

<

>

>
>
<

>

1

2

3

4

5

6

7

8

9

10

Vrms

Arms

Vthd

Athd

W

PF

Vh

3

1

2

3

4

7

8

5

6