Rockwell Automation Publication 1412-UM001D-EN-P - September 2012

Chapter 4

DATAVIEW Software

Alarm Conditions Configuration

The Alarm Conditions window lets you set up 10 alarm configurations.

Figure 6 - Alarm Conditions Window

Hysteresis: This value for alarms is set to prevent multiple recordings of an

event that goes above the threshold and a certain percentage below it at

times.

Disable All Alarms: When this box is checked, all alarms will be disabled

even if the individual alarm enable box is checked.

Enabled: When check box is checked, alarm is enabled.
Capture Parameter: The Alarm will be triggered based on the value of the

selected parameter.
Choices include:
None: no alarm
Vunb: voltage unbalance
Vrms: voltage root mean squared
Aunb: current unbalance
Urms: voltage phase minus phase root mean squared
Hz: frequency
Akf: current K factor
Arms: current root mean squared
Vthd: voltage total harmonic distortion
VPST: voltage short term flicker
Uthd: voltage phase minus phase total harmonic distortion
Vcf: voltage crest factor
Ucf: voltage phase minus phase crest factor

EXAMPLE

Alarm threshold is 100V or higher, hysteresis is 1%. When the voltage goes up
to 100V, the alarm condition starts. When the voltage goes back down to 99V,
the alarm condition stops.