Feature select group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual

Page 100

Advertising
background image

Chapter 5 – Programming

5-32

Feature Select Group (cont.)

[Balance Freq]

Parameter # 80

Factory Default 0 Hz

[Balance Freq]

Parameter Type Read & Write

Minimum 0 Hz

This parameter selects the frequency at which balance
detection is performed.

Units 1 Hertz

Maximum 255 Hz

[Balance Time]

Parameter # 79

Factory Default 0 Sec

[Balance Time]

Parameter Type Read & Write

Minimum 0 Sec

This parameter determines the amount of delay time
before a valid output occurs. The delay time begins when
the drive reaches [Balance Freq]. The output contact will
be closed when balanced and open when unbalanced.

Units 0.1 second

Maximum 255 Sec

[Balance Angle]

Parameter # 78

Factory Default 0

[Balance Angle]

Parameter Type Read & Write

Minimum 0

This parameter determines the acceptable variation in
phase angle which is set between a balanced condition
and an unbalanced condition. A balance condition is
defined as a variation which is less than the ‘Balance
Angle’ setting. [Output 1 Config] or [Output 2 Config]
can be set to ‘‘Balance” to indicate when a balanced
condition exists.

Maximum 255

Figure 5.18 Motor Unbalance

Phase Angle

V

ariation

0

255

[Balance Angle]

Detection Window

–.5 Hz

+1.0 Hz

[Balance Freq]

y