Chapter 5 – Programming

5-18

Advanced Set Up Group (cont.)

[Start Boost]

Parameter # 48

Factory Default 0 Volts

[Start Boost]

Parameter Type Read & Write

Minimum 0 Volts

This parameter sets the DC boost level for acceleration
when [DC Boost Select] is set to ‘‘Run Boost” or ‘‘Break
Point.”

Units 1 Volt

Maximum 25% of Max. Drive Rated Volts

Figure 5.10 Start/Run Boost

[Base Voltage]
[Base Frequency]

b

0 –

0

Voltage

Frequency

[Start Boost]

'

[Run Boost]

'

Active when [DC
Boost Select] is
set to
‘‘Run Boost”

a 150% of Start Boost

a 150% of Run Boost

[Run Boost]

Parameter # 83

Factory Default 0 Volts

[Run Boost]

Parameter Type Read & Write

Minimum 0 Volts

This parameter sets the DC boost level for constant speed
level when [DC Boost Select] is set to ‘‘Run Boost.” [Run
Boost]
must be set at a value less than [Start Boost].

Units 1 Volt

Maximum 25% of Max. Drive Rated Volts