Advanced set up group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual
Page 86
Chapter 5 – Programming
5-18
Advanced Set Up Group (cont.)
[Start Boost]
Parameter # 48
Factory Default 0 Volts
[Start Boost]
Parameter Type Read & Write
Minimum 0 Volts
This parameter sets the DC boost level for acceleration
when [DC Boost Select] is set to ‘‘Run Boost” or ‘‘Break
Point.”
Units 1 Volt
Maximum 25% of Max. Drive Rated Volts
Figure 5.10 Start/Run Boost
[Base Voltage]
[Base Frequency]
b
0 –
0
Voltage
Frequency
[Start Boost]
'
[Run Boost]
'
Active when [DC
Boost Select] is
set to ‘‘Run Boost”
a 150% of Start Boost
a 150% of Run Boost
[Run Boost]
Parameter # 83
Factory Default 0 Volts
[Run Boost]
Parameter Type Read & Write
Minimum 0 Volts
This parameter sets the DC boost level for constant speed
level when [DC Boost Select] is set to ‘‘Run Boost.” [Run
Boost] must be set at a value less than [Start Boost].
Units 1 Volt
Maximum 25% of Max. Drive Rated Volts