Diagnostics group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual

Page 108

Advertising
background image

Chapter 5 – Programming

5-40

Diagnostics Group (cont.)

[Freq Source]

Parameter # 62

[Freq Source]

Parameter Type Read

This parameter displays the frequency source currently
commanding the drive.

Units None

Displays ‘‘Remote Pot”

‘‘0-10 Volt”
‘‘4–20 mA”
‘‘MOP”
‘‘Adapter 1”
‘‘Adapter 2”
‘‘Adapter 3”
‘‘Adapter 4”
‘‘Adapter 5”
‘‘Adapter 6”

‘‘Preset 1”
‘‘Preset 2
‘‘Preset 3”
‘‘Preset 4”
‘‘Preset 5’’
‘‘Preset 6”
‘‘Preset 7”

[Freq Command]

Parameter # 65

Factory Default 0.00 Hz

[Freq Command]

Parameter Type Read Only

Minimum 0 Hz

This parameter displays the frequency that the drive is
commanded to output. This command may come from any
one of the frequency sources selected by [Freq Select 1],
[Freq Select 2] or [Preset Freq 1-7] as determined by
inputs to SW1, SW2 and SW3 at TB2.

Units 0.01 Hz

Maximum 400.00 Hz

[Drive Direction]

Parameter # 69

Factory Default ‘‘Forward’’

[Drive Direction]

Parameter Type Read Only

Minimum

This parameter displays the running direction of the drive.

Units None

Displays ‘‘Forward”

‘‘Reverse”

[Motor Mode]

Parameter # 43

[Motor Mode]

Parameter Type Read Only

This parameter is used for internal diagnostic purposes.