Chapter 5 – Programming

5-12

Set Up Group (cont.)

[Overload Mode]

Parameter # 37

Factory Default “No Derating”

[Overload Mode]

Parameter Type Read & Write

This parameter selects the derating factor for the I

2

t

electronic overload function. Designed to meet NEC Article

Units None

Settings ‘‘No Derating”

10:1 Speed Range
– No Derating Refer to Figure 5.2

electronic overload function. Designed to meet NEC Article
430 and UL (file E59272) equivalent requirements.
Additional overload devices do not need to be installed.

‘‘Min Derate”

4:1 Speed Range
– Derate below 25% of Base Speed.
Refer to Figure 5.3

‘‘Max Derate”

2:1 Speed Range
– Derate below 50% of Base Speed.
Refer to Figure 5.4

100

80
60

40

20

0

25 50 75 100 125 150 175 200

% Base Speed

Figure 5.2 No Derating

100

80
60

40

20

100

80
60

40

20

Figure 5.3 Min Derating

Figure 5.4 Max Derating

% Base Speed

% Base Speed

0

25 50 75 100 125 150 175 200

0

25 50 75 100 125 150 175 200

[Overload Current]

% of

Setting

[Overload Current]

% of

Setting

[Overload Current]

% of

Setting

[Overload Current]

Parameter # 38

Factory Default 115% of Drive Rated Current

Displayed in Amps

[Overload Current]

Th s v ue sh u d e se

he

r

ep e u

d

Parameter Type Read & Write

Minimum 20% of Drive Rated Current

Displayed in Amps

This value should be set to the motor nameplate Full Load
Amps (F.L.A.).

Units 0.1 Amps

Maximum 115% of Drive Rated Current

Displayed in Amps