Faults group (cont.) – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual

Page 104

Advertising
background image

Chapter 5 – Programming

5-36

Faults Group (cont.)

Line Loss Fault “U Volt Run” (Disabled)

Line Loss Fault “F03 Enable” (Enabled)

No Fault

No Fault

No Fault

Power Loss Fault

Undervolt
Fault

100% Nominal
Bus Voltage

85% Nominal
Bus Voltage

Minimum Bus
Voltage

T0

T1 T2

T3

100% Nominal
Bus Voltage

85% Nominal
Bus Voltage

Minimum Bus
Voltage

T0

T1 T2

T3

Undervolt
Fault

➀ Minimum bus voltage is approximately 70% of Line Voltage

Output Power is on

Output Power is on

No Output Power

No Output

Power

Output Power is on

IMPORTANT:If line loss is set to ‘‘U Volt Run” and ‘‘Run On Power Up” is enabled, the drive will run as long as the bus voltage
is high enough to maintain logic.

[Flt Clear Mode]

Parameter # 39

Factory Default ‘‘Enabled”

[Flt Clear Mode]

Parameter Type Read & Write

This parameter controls the method for clearing faults.

Units None

Setting ‘‘Enabled”

Faults Cleared By Issuing a Valid Stop Command or
Cycling Input Power

‘‘Disabled”

Faults Cleared Only By Cycling Input Power