Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual

Page 43

Advertising
background image

Chapter 3 – Human Interface Module

3-5

HIM MODES

The HIM has up to seven different modes. Refer to Figure 3.3.

Display

When selected, the Display mode allows any of the parameters
to be viewed. However, parameter modifications are not
allowed.

Process

The Process mode allows a “configurable” display to be
programmed. One user selected parameter can be displayed
with programmed text and scaling. Refer to Chapter 5 for
further information.

Program

Program mode provides access to the complete listing of
parameters available for programming. Refer to Chapter 5 for
further parameter programming information.

EEPROM

This mode allows all parameters to be reset to the factory
default settings.

Search (HIM Software Versions 3.00 and Above Only)

This mode will search for parameters that are not at their
default values.

Control Status (HIM Software Versions 3.00 and Above Only)

Permits the [Logic Mask] parameter to be disabled/enabled
allowing HIM removal while drive power is applied. This menu
also provides access to a fault queue which will list the last four
faults that have occurred. “Trip” displayed with a fault
indicates the actual fault that tripped the drive. A clear function
clears the queue.

IMPORTANT: Clearing the Fault Queue will not clear an
active fault.

Password

The Password mode protects the drive parameters against
programming changes by unauthorized personnel. When a
password has been assigned, access to the Program and
EEPROM modes can only be gained when the correct password
has been entered. The password can be any five digit number
between 00000 and 65535. Refer to the example on page 3-16.