Chapter 4 – Start–Up

4-2

Initial Operation - Motor Disconnected

1.Verify that AC line power at the disconnect device is within

the rated value of the drive.

2.Disconnect and lock-out all incoming power to the drive

including incoming AC power to terminals L1, L2 and L3 (R,
S and T) plus any separate control power for remote interface
devices. Remove the drive cover and verify the motor leads
are disconnected from the Power Terminal Block (TB1),
terminals T1, T2 and T3 (U, V, W). Refer to Chapter 2 for
terminal location.

ATTENTION: Proceed with caution. A DC Bus
Voltage may be present at the Power Terminal
Block (TB1) even when power is removed from
the drive.

3.Verify that the Stop and Enable inputs are present.

4.Confirm that all other optional inputs are connected to the

correct terminals and are secure.

5.If the HIM has a Control Panel, use the local controls to

complete the start-up procedure. If a Control Panel is not
present, remote devices must be used to operate the drive.

6.Replace the drive cover.

ACTION

DESCRIPTION

HIM DISPLAY

Apply

Power to Drive

❏ 7. When power is first applied to the drive, the following information will be

momentarily displayed:

a.) The HIM ID# (Adapter #) and firmware version number.

b.) Communication status.

c.) Series letter of drive is displayed.

d.) The LCD Display should light and display a drive status of ‘‘Stopped”

and an output frequency of ‘‘+0.00 Hz.”

AC DRIVE
Series X

HIM ID #
Connecting...

HIM ID #
Version X.XX

Stopped
+0.00 Hz

HIM ID #
Connected