Chapter 6 – Troubleshooting and Fault Information

6-5

Table 6.B Bulletin 1305 Fault Descriptions (cont.)

Fault Name & Number

Fault Description

Action to Take

Motor Mode FIt

2

Internal error.

Reset drive to factory defaults.

Motor Mode FIt
F24

Internal error.

Reset drive to factory defaults.

Motor Stall Fault
F6

The motor is stalled.

If the motor is drawing excessive current, the motor load is
excessive and will not allow the drive to accelerate to set speed.
A longer accel time or a reduced load may be required.

Neg Slope Fault
F35

Drive software detected a portion of the volts/Hz curve with a
negative slope.

Check drive programming.

1. [Maximum Voltage] parameter must be greater than or

equal to [Base Voltage].

2. [Base Voltage] parameter must be greater than 1.5 X [Start

Boost].

3. If the [DC Boost Select] parameter is set to ‘‘Break Point,’’

[Base Voltage] must be greater than [Break Voltage] and
[Break Voltage] must be greater than [Start Boost].

4. [Maximum Freq] must be greater than or equal to [Base

Frequency]

Network Error

Network Error 0 – Error 6

ScanPort Error

Network Error 7 – Error 9

Communications Error

1. Press the “Up” or “Down” arrow to clear the message from

the HIM display.

2. Unplug the HIM from the cable or drive and re-connect.
3. Check for external noise sources.