Chapter 5 – Programming

5-28

[Skip Freq Band]

Parameter # 35

Factory Default 0 Hz

[Skip Freq Band]

Parameter Type Read & Write

Minimum 0 Hz

This parameter determines the band width around a [Skip
Frequency]
. The actual band width is 2

 [Skip Freq

Band] – 1/2 the band above and 1/2 the band below the
[Skip Frequency] setting. “0” Disables All Skip
Frequencies.

Units 1 Hz

Maximum 15 Hz

'

Figure 5.15 Skip Frequency Band

b

y

Two times

[Skip Freq Band]

Setting

'

Command Frequency

Skip Frequency

Frequency

Time

Drive Output
Frequency

Setting

a

[MOP Increment]

Parameter # 22

Factory Default 0.00 Hz/Sec

[MOP Increment]

Parameter Type Read & Write

Minimum 0.00

This parameter sets the rate of increase or decrease to
the [MOP Hertz] command frequency. IMPORTANT:
The MOP function can only be invoked through a serial
communications module.

Units 1 Hz/Sec

Maximum 255 Hz/Sec