Appendix A –

Block Diagram and Specifications

A-3

Table A.1 Specifications (cont.)

ENVIRONMENTAL SPECIFICATIONS

Enclosure

NEMA 1 (IP30) standard

Ambient Temperature

0 to 50

_C; Optional Enclosures: 0 to 40_C

Storage Temperature

-40

_C to 70_C

Relative Humidity

0 to 95% (non condensing)

Vibration

1.0 G Operational

Cooling Method

Natural Convection (no fans)

Altitude

Above 1,000 m (3,300 ft), derating at 6% of drive rated amps per 1000 m

CONTROL INPUTS

Control Input Type

Contact closure (Internal 5V supply)

DO NOT apply external voltage

Start
Stop
Forward/Reverse

Configurable Inputs for 2 or 3 wire control

Jog

Momentary (non-maintained) Input

SW1
SW2
SW3

Configurable Inputs for control of 7 Preset speeds and 2 Accel/Decel times

Enable

Interlock Input to enable drive operation

External Speed
Potentiometer

10 K Ohms, 1 Watt

Analog Input
(4 to 20mA)

Input lmpedance 250 Ohms (Non-Isolated), 10 bit resolution

Analog Input
(0 to 10 V DC)

Input Impedance 100 K Ohms (Non-Isolated), 10 bit resolution