Set up – Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual

Page 76

Advertising
background image

Chapter 5 – Programming

5-8

Set Up

This group of parameters defines the basic operation of the drive and should be programmed before initial
operation. For advanced programming and information on specific parameters, refer to the flow chart on
page 5-2 & 5-3

[Input Mode]

Parameter # 21

Factory Default “3 wire”

[Input Mode]

Parameter Type Read & Write

This parameter selects between three wire and Run
Fwd/Rev control. Refer to Chapter 2, Figure 2-5.
IMPORTANT: If this parameter is changed while the drive is
operating, power must be cycled to the drive for the change
to take effect. This is required since the start and reverse
functions will operate differently for the two different modes.

Units None

Setting “3 Wire”

“Run Fwd/Rev”

IMPORTANT: This parameter cannot be pro-
grammed while the drive is running.

[Freq Select 1]

Parameter # 5

Factory Default “Adapter 1”

[Freq Select 1]

Parameter Type Read & Write

Settings ‘‘Remote Pot”

‘‘0-10 Volt”
‘‘ –2

‘‘Preset 1”
‘‘Preset 2”
‘‘ rese

This parameter is the factory default parameter for
selecting the frequency source that will supply the [Freq
Command]
to the drive. [Freq Select 2] or [Preset Freq
1–7]
can be selected in place of this parameter with proper
terminal block inputs. (See Charts on Pages 5-26 and
5-27).

Units None

‘‘4–20 mA”
‘‘MOP”
‘‘Adapter 1”
‘‘Adapter 2”
‘‘Adapter 3”
‘‘Adapter 4”
‘‘Adapter 5”
‘‘Adapter 6”

‘‘Preset 3”
‘‘Preset 4”
‘‘Preset 5’’
‘‘Preset 6”
‘‘Preset 7”

[Accel Time 1]

Parameter # 7

Factory Default 10.0 Sec

[Accel Time 1]

Parameter Type Read & Write

Minimum 0.0 Sec

This parameter is the factory default parameter for
determining the time it will take the drive to ramp from 0 Hz
to [Maximum Frequency]. The rate is linear unless
[S Curve] is ‘‘Enabled.” It applies to any increase in
command frequency. The [Accel Time 2] parameter can
be selected in place of this parameter. (See Charts on
Pages 5-26 and 5-27).

Units 0.1 Second

Maximum 3600.0 Sec

Advertising