Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual

Page 16

Advertising
background image

Chapter 1 – Information and Precautions

1-6

Table 1.A Drive Rating and Derating Guidelines

a alo

Motor Rating

Voltage

a n

Catalog

er

3

O Input

1

O Input

ol a e

Rating

Number

IP30

HP

kW

Output ➀➁

Current (A)

HP

kW

Output ➀➁

Current (A)

1305-AA02A

1/2

0.37

2.3

200-230V

/6

1305-AA03A

3/4

0.55

3

1/2

0.37

2.3

2

2

50/60 Hz

1305-AA04A

1

0.75

4.5

3/4

0.55

3

1305-AA08A

2

1.5

8

1

0.75

4.5

1305-AA12A

3

2.2

12 ➂

2

1.5

8 ➂

1305-BA01A

1/2

0.37

1.3

380-460V

/6

1305-BA02A

3/4

0.55

1.6

8

6

50/60 Hz

1305-BA03A

1

0.75

2.3

N

v

e

1305-BA04A

2

1.5

4

Not Available

1305-BA06A

3

2.2

6 ➃

1305-BA09A

5

4.0

9 ➄

In general:

When operating the drive in an ambient temperature at or near
the maximum operating temperature (50

°

C), the following

derating guidelines are recommended to guard against
overheating depending on application and operating conditions.

Motor Full Load Amps (FLA) should not exceed the drive output current rating.

If the [PWM Frequency] is set above 4kHz, the output current must be derated per the
chart on page 5-20.

Output current value listed for 200V input voltage. At 230V input voltage, output
current is 9.6A for 3 phase and 6.8A for single phase.

Output current value listed for 380V input voltage. At 415V input voltage, output
current is 5.3A. At 460V input voltage, output current is 4.8A.

Output current value listed for 380V input voltage. At 415V input voltage, output
current is 8.4A. At 460V input voltage, output current is 7.6A.