Chapter 5 – Programming

5-35

Faults

This group of parameters provides information and programmed settings on commonly viewed drive faults.

[Fault Buffer 0-3]

Parameter # 86-89

Factory Default None

[Fault Buffer 0-3]

Parameter Type Read Only

These parameters store the last (4) faults that occur. If the
same fault occurs multiple times in a row, it will only be
stored once. [Fault Buffer 0] through [Fault Buffer 3] can
only be cleared by ‘‘Reset Defaults” from EEPROM mode
or [Set Defaults] parameter. This will leave a ‘‘F48” in
[Fault Buffer 0].

Units None

Buffer

0
1

2
3

Last Fault, stored in EEPROM
Fault from Buffer 0, Stored in EEPROM
Fault from Buffer 1, Stored in EEPROM
Fault from Buffer 2, Stored in EEPROM

[Clear Fault]

Parameter # 51

Factory Default ‘‘Ready”

[Clear Fault]

Parameter Type Read & Write

This parameter is used to clear a fault and return the drive
to ready status if the fault condition no longer exists.
IMPO TA T: C e r

u ]

s p ru

g dr ve

s

Units None

Displays ‘‘Ready”

Display after function complete

IMPORTANT: [Clear Fault] will stop a running drive. Also
[Clear Fault] does not clear [Fault Buffer 0] through
[Fault Buffer 3].

‘‘Clear Fault”

Attempts to clear fault

[Cur Lim Trip En]

Parameter # 82

Factory Default ‘‘Default Run”

[Cur Lim Trip En]

Parameter Type Read & Write

This setting determines whether or not exceeding the
se

g

[

rren L

use D g s

Curre

Units None

Setting ‘‘Trip @ I Lim”

A Diagnostic Current Limit Fault is generated

setting in [Current Limit] will cause a Diagnostic Current
Limit Fault (Fault F36).

‘‘Default Run”

No fault generated

[Line Loss Fault]

Parameter # 40

Factory Default ‘‘F03 Enable”

[Line Loss Fault]

Parameter Type Read & Write

This setting determines whether a 15% drop in DC Bus
v

ge

h ve

e e

per

r

use ‘‘

er

Units None

Setting ‘‘UVolt Run”

‘‘Power Loss Fault” Disabled

voltage will have no effect on operation or cause a ‘‘Power
Loss Fault” (fault F03).

‘‘FO3 Enable”

Drive Trips at 85% of nominal bus voltage.