Chapter 5 – Programming

5-9

Set Up Group (cont.)

[Decel Time 1]

Parameter # 8

Factory Default 10.0 Sec

[Decel Time 1]

Parameter Type Read & Write

Minimum 0.0 Sec

This parameter is the factory default parameter for
determining the time it will take the drive to ramp from
[Maximum Frequency] to 0 Hz. The rate is linear unless
[S Curve] is ‘‘Enabled” or [Stop Select] is set to
‘‘S-Curve.” It applies to any decrease in command
frequency. The [Decel Time 2] parameter can be selected
in place of this parameter. (See Chart on Page 5-26).

Units 0.1 Second

Maximum 3600.0 Sec

Max. Frequency

'

Accel

Time

'

a

Decel

Time

a

'

Speed

Time

0

0

Figure 5.1 Accel/Decel Time

[Base Frequency]

Parameter # 17

Factory Default 60 Hz

[Base Frequency]

Parameter Type Read & Write

Minimum 40 Hz

This value should be set to the motor nameplate Rated
Frequency.

Units 1 Hz

Maximum 400 Hz

[Base Voltage]

Parameter # 18

Factory Default Max. Drive Rated Volts

[Base Voltage]

Parameter Type Read & Write

Minimum 25% of Max. Drive Rated Volts

This value should be set to the motor nameplate Rated
Voltage.

Units 1 Volt

Maximum 100% of Max. Drive Rated Volts