Chapter 6 – Troubleshooting and Fault Information

6-4

Table 6.B Bulletin 1305 Fault Descriptions (cont.)

Fault Name & Number

Fault Description

Action to Take

HIM

Drive

Error 1 – The checksum read from the HIM’s EEPROM does not
match the checksum calculated from the EEPROM data.

Error 2 – The number of parameters in saved profile does not
equal master.

Error 3 – Download was attempted to a different type drive
(i.e. 1336->1305).

Error 4 – Saved data for parameter not correct for new drive.

Error 5 – Drive is running while attempting download.

Repeat operation. Old profile corrupt. Save new profile. Repeat
operation.

The last parameter programmed will be displayed on the top
line. Verify that all parameters have been programmed. If not,
manually program any remaining parameters.

Download can only take place with the same type of drive.

Capabilities of drive are different than the master drive. Press
Enter to continue download. When download is complete,
manually program the parameter where the error occurred.

Stop drive, then perform download.

IPM Current Fault
F44

The internal power module overcurrent limit had been exceeded. Check for short circuit at the drive output or excessive load

conditions at the motor, specifically cable capacitance to ground.

IPM Overtemp Fault
F45

The internal power module thermal limit has been exceeded.

Check for blocked or dirty heat sink fins. Check for proper
mounting and spacing (See page 2-1). Check if the ambient
temperature limit has been exceeded.

Max Retries Fault
F33

Drive unsuccessfully attempted to reset a fault and resume
running for the programmed number of [Reset/Run Tries].

Check fault buffer for fault code requiring reset. Correct the
cause of the fault and manually clear by cycling the stop
command or cycling power.