Rockwell Automation 1305 AC Drive, Firmware 1.01-3.00 User Manual User Manual

Page 64

Advertising
background image

Chapter 4 – Start–Up

4-6

❏ 12. Verifying Minimum and Maximum Frequency Settings.

or

a.) Press the Start key. The drive should output zero Hz. which is the

factory default value for the [Minimum Freq] parameter. The Status
Display should indicate “At Speed” and the actual frequency (+0.00
Hz.).

b.) With the drive still running, use the speed source to command

maximum speed. The drive should ramp to 60 Hz. which is the factory
default value for the [Maximum Freq] parameter.

At Speed
+0.00 Hz

Accelerating

+29.62 Hz

At Speed

+60.00 Hz

❏ 13. Enable interlock check.

The following steps check for correct drive operation when the Enable
input is removed. Refer to Chapter 2 for terminal designations.

At Speed
+60.00Hz

Open Enable Signal

Restore Enable Signal

a.) With the drive still running, open the Enable signal. The drive should

stop and indicate “Not Enabled” on the Display Panel. Restore the
Enable signal.

b.) Restart the drive by pressing the Start key.

c.) Stop the drive.

Not Enabled

+0.00 Hz

Accelerating

+10.00 Hz

Stopped
+0.00 Hz

Advertising