F - electronic keying, Specifying electronic keying, Appendix f – Rockwell Automation 1756-ENET/B ControlLogix Ethernet Communication Interface Module User Manual User Manual

Page 115: Electronic keying, Appendix

Advertising
background image

1

Publication 1756-UM051B-EN-P - November 2000

Appendix

F

Electronic Keying

Specifying Electronic
Keying

You specify electronic keying to ensure that a module being inserted
or configured is of the proper type and firmware revision.

ATTENTION

!

Be extremely cautious if you disable electronic
keying. If used incorrectly, this option can lead
to personal injury or death, property damage, or
economic loss.

Keying

Description

“least”

disable keying

No attributes of the software or hardware are
required to match.

“moderate”

compatible module

The module must be compatible with the software
configuration. These characteristics must match:

module type

catalog number

major revision

The minor revision must be equal to or greater than
the one specified in the software.

“most”

exact match

The module must match the software configuration
exactly. These characteristics must match:

module type

catalog number

major revision

minor revision