Publication 1756-UM051B-EN-P - November 2000

Analog I/O with Direct Connection 6-7

8. Click on Channel 0 and enter the following Scaling parameters:

9. Click on Next twice to access the Limits page.

10.Enter the following Limits:

11.Click on Finish to save the configuration.

The I/O Configuration tree should now look similar to the one
shown below.

High Signal

High Engineering

10.0 V

8000

(1)

(1)

This scaling is selected to use the 13-bit voltage
resolution of the 1756-OF8. See specifications in
publication 1756-6.5.9 for more information.

Low Signal

Low Engineering

0.0 V

0

High Clamp

8000

Low Clamp

0