Publication 1756-UM051B-EN-P - November 2000

5-16 Rack Optimized I/O

Test the Example
Application

You will test the example application by using a momentary switch to
simulate a parts sensor.

1. Wire the 1756-IB16I digital input module as shown in the following

figure:

2. Restore the RSLogix5000 software and place the controller in Run

mode.

3. Repeatedly press and release the momentary switch at IN-0 (Count)

on the 1756-IB16I digital input module. Each time you press the
switch you should see the Parts_Count accumulated value
increment on the screen and the LED display of the OB16I output
module increment in binary.

4. Press and release the momentary switch at IN-1 (Reset) on the

1756-IB16 digital input module. You should see the accumulated
value of the Parts_Count reset to zero and all of the LEDs on the
1756-OB16I output module turn off.

IN-0

IN-1

GND-0

1

3

2

+

1756-IB16I

24V

Count

Reset

GND-1

4

Accumulated Value
will increment and
be moved to Output
module.

LED display will

increment in

binary count