A - led status indicators, Interpreting the status indicators, Appendix a – Rockwell Automation 1756-ENET/B ControlLogix Ethernet Communication Interface Module User Manual User Manual

Page 97: Led status indicators, Appendix

Advertising
background image

1

Publication 1756-UM051B-EN-P - November 2000

Appendix

A

LED Status Indicators

Interpreting the Status
Indicators

The faceplate of the 1756-ENET/B module is provided with LED
indicators that display the module status and transmit/receive status.
The following table describes module health indicator displays,
module status, and recommended action:

The following table describes the displays of the transmit (TX) and
receive (RX) indicators:

Detailed network diagnostics are provided by the module’s Web
pages, which can be accessed through Netscape or Microsoft Internet
Explorer. See Appendix B.

If the OK indicator is:

then module status is:

take this action:

Off

Not operating.

Apply chassis power.
Verify module is completely
inserted into chassis and
backplane.

Red, then flashing red
or flashing green

Performing powerup
diagnostics.

None, normal operation.

Green

Operating.

None.

Red flashing

Not configured.

Configure the module.

Red

Unrecoverable fault.

Repair or replace module.

If this indicator: is:

the module is:

TXD

Green

Transmitting data

Off

Not active

RXD

Green

Receiving data

Off

Not active

31153-M

AUI

10 BASET

1756-ENET

RXD TXD OK

ETHERNET

TXD
Indicator

OK Indicator

RXD
Indicator

Front View