Rockwell Automation 1746-INT4 Thermocouple/MV Isolated/ User Manual User Manual

Page 20

Advertising
background image

Publication 1746-UM614B-EN-P - September 2007

20 Quick Start

6. Set up Channel 0.

Determine the operating parameters for channel 0. This example
shows the channel 0 configuration word defined with all
defaults (0) except for the channel enable (bit 11=1). Module
assumed in slot 1. (For details on channel configuration, refer to
the configuration worksheet on page 22).

7. Program the transfer of the configuration word.

Program the transfer of the configuration word (from step 6) to
the module.

a. Using the memory map function, create integer file N10.

Integer file N10 should contain one element for each channel
used. (For this example, we used N10:0.).

b. Enter configuration parameters for channel 0 (from step 6)

into N10:0.

In this example, all of the bits of N10:0 are zero except for the
channel enable bit (N10:0/11).

c. Program a ladder logic instruction to copy the contents of

N10:0 to output word O:1.0.

O:1.1

Channel 1 Configuration Word

Channel 2 Configuration Word

Channel 3 Configuration Word

Words 4, 6, & 7

(reserved)

Bit 15

Bit 0

Word 1

Word 2

Word 3



Address

O:1.0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Channel 0 Configuration Word

Word 0

Word 7

Input

Type

Data Format

Open

C

ircuit

Temperature Units

C

hannel Enable

Unused

0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0

Use Default Settings For:

Example Settings for Channel 0.

• Type J Thermocouple
• Engineering Units x 1
• Data Word = 0 If Open Circuit
• Degrees Celsius

O:1.2
O:1.3

O:1.7



Unused

Calibration Word 5



SLC 500 Controller
Data Files

Input Image

Output Image
(8 words)

Set this bit (11) to enable channel. Address = O.1.0/11.