Rockwell Automation 1746-INT4 Thermocouple/MV Isolated/ User Manual User Manual

Page 54

Advertising
background image

Publication 1746-UM614B-EN-P - September 2007

54 Channel Configuration, Data, and Status

Channel Status Word, Channels 0…3 (I:e.4 through I:e:.7) — Bit Definitions

Bit or
Bits

Reflect/
Indicate

Configured for

With This Bit Code

Reflects Configuration in
Bits 0…11 and Indicates
Detected Faults in Bits
12…15

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 … 3

Input
Type

TC Type J

0 0 0 0

Reflects the type of channel
input.

TC Type K

0 0 0 1

TC Type T

0 0 1 0

TC Type E

0 0 1 1

TC Type R

0 1 0 0

TC Type S

0 1 0 1

TC Type B

0 1 1 0

TC Type N

0 1 1 1

±50 mV

1 0 0 0

±100 mV

1 0 0 1

TC Type C

1 0 1 0

TC Type D

1 0 1 1

Invalid

1 1 0 0 The module faults when it

detects an invalid
configuration.

Invalid

1 1 0 1

Invalid

1 1 1 0

CJC Temp

1 1 1 1

4, 5

Data
Format

Engr. Units x1

0 0

Reflects the type of data
format.

Engr. Units x10

0 1

Scaled-for-PID

1 0

Counts

1 1

6, 7

Open
Input
Mode

Zero

0 0

Reflects module response to a
detected open input circuit (for
all input types including CJC
thermistor). The module faults
when it detects an invalid
configuration.

Upscale

0 1

Downscale

1 0

Invalid

1 1

8

Units
°F, °C

Degrees C

0

Reflects temperature units.

Degrees F

1

9, 10

Unused

Unused

0

0

Faults when it detects a
non-zero value.

11

Chnl
Enable

Channel Off

0

Reflects enabled/disabled
channel status. Status word of
a disabled channel is zero.
Channel data and status words
remain cleared until the
module sets this bit in
response to a new
configuration word.

Channel On

1

Advertising