Channel Configuration, Data, and Status 55

Detected Faults Indicated by Bits 12…15

When the module detects any of the conditions described for bits
12…15, it:

sets the corresponding bit.

blinks the status LED on the front panel for the channel having
the fault.

The module is designed to detect the following fault conditions.

Open-circuit Detection (Bit 12)

The module tests all enabled channels for an open-circuit condition
each time it scans its inputs. Possible causes of an open circuit
include:

broken thermocouple or CJC thermistor.

thermocouple or CJC thermistor wire cut or disconnected.

12

Open
Input

Diagnostics

0

Condition not detected.

1

Detected open input.

13

Under-
range

Diagnostics

0

Condition not detected.

1

Detected under-range input.

14

Over-
range

Diagnostics

0

Condition not detected.

1

Detected over-range input.

15

Invalid
Config

Diagnostics

0

Condition not detected.

1

Detected invalid configuration.

Channel Status Word, Channels 0…3 (I:e.4 through I:e:.7) — Bit Definitions (Continued)

Bit or
Bits

Reflect/
Indicate

Configured for

With This Bit Code

Reflects Configuration in
Bits 0…11 and Indicates
Detected Faults in Bits
12…15

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0