74 Application Programming Examples

Channel Configuration

All channels are configured for:

display temperature to tenths of a degree.

zero data word in the event of an open-circuit.

Configuration setup for ambient thermocouple:

channel 0.

type T thermocouple.

Configuration setup for bath thermocouple:

channel 1.

type J thermocouple.

Configuration setup for steam thermocouple:

channel 2.

type K thermocouple.

Configuration setup for chilled H

2

O thermocouple:

channel 3.

type J thermocouple.

Configuration setup for cabinet temperature:

channel 0.

CJC temperature.

Configuration Word

12

13

14

15

8

6

7

4

1

2

3

0

0

1

0

0

0

0

x

0

0

0

0

0

0

1

0

0

0

1

0

0

0

0

x

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

x

0

0

0

0

0

0

0

1

0

0

1

0

0

0

0

x

0

0

0

0

0

0

0

0

Channel 0

Channel 1

Channel 2

Channel 3

(Ambient)

(Bath)

(Steam)

(Chilled H2O)

0

0

1

0

0

0

0

x

0

0

0

0

1

1

1

1

Channel 3

(Cabinet)

9

10

5

0

11

Not Used

Channel
Enable
0 = Disable
1 = Enable

Not
Used

Temp
Units
0 = °C
1 = °F

Response to
Open-circuit
0 0 = zero
0 1 = FS
1 0 = LS

Data
Format
0 0 = EU x1
0 1 = EU x10
1 0 = Scaled PID
1 1 = Prop Counts

Type
of Input
0 0 0 0 = Type J
0 0 0 1 = Type K
0 0 1 0 = Type T
0 0 1 1 = Type E
0 1 0 0 = Type R
0 1 0 1 = Type S

0 1 1 0 = Type B
0 1 1 1 = Type N
1 0 0 0 = 0…100 mV
1 0 0 1 = ±100
1 0 1 0 = Type C
1 0 1 1 = Type D
1 1 1 1 = CJC Temp