Publication 1746-UM614B-EN-P - September 2007

72 Application Programming Examples

Configuration Word

address 15 data 0 address 15 data 0
N10:0 0000 1001 0001 0000

11

12

13

14

15

8

6

7

4

1

2

3

0

0

1

0

0

0

0

1

0

0

0

1

0

0

0

0

9

10

5

0

15

] [

S:1

MOVE
Source

N10:0

Dest

O:3.0

MOV

TO BCD
Source

I:3.0

Dest

N7:0

TOD

MASKED MOVE
Source

N7:0

Mask

0FFF

Dest

O:2.0

MVM

*

END

Example Configuration Word with These Parameters:
channel enabled, °F, zero for open-circuit, EU x10, Type J thermocouple

Not Used

Channel
Enable
0 = Disable
1 = Enable

Not Used

Temp
Units
0 = °C
1 = °F

Response to
Open-circuit
0 0 = zero
0 1 = FS
1 0 = LS

Data
Format
0 0 = EU x1
0 1 = EU x10
1 0 = Scaled PID
1 1 = Prop Counts

Type
of Input
0 0 0 0 = Type J
0 0 0 1 = Type K
0 0 1 0 = Type T
0 0 1 1 = Type E
0 1 0 0 = Type R
0 1 0 1 = Type S

0 1 1 0 = Type B
0 1 1 1 = Type N
1 0 0 0 = 0…100 mV
1 0 0 1 = ±100
1 0 1 0 = Type C
1 0 1 1 = Type D

First Pass Bit

Rung 2.0

Rung 2.1

Convert the channel 0 data word (° F) to BCD and write this to the LED indicator display.

Initialize Channel 0

Program

The use of the masked move instruction with the 0FF mask lets you use outputs 12, 13, 14 and 15 for other
output devices in your system. The seven segment display uses outputs 0 …11.

Rung 2.2

Data Table