Program – Rockwell Automation 1746-INT4 Thermocouple/MV Isolated/ User Manual User Manual

Page 76

Advertising
background image

Publication 1746-UM614B-EN-P - September 2007

76 Application Programming Examples

Program

The first six rungs change channel configurations based on the
position of the two selector switches.

0

] [

I:2.0

OSR

B3

0

COP

COPY FILE
Source

#N10:0

Dest

#O:1.0

Length

4

0

] [

I:2.0

OSR

B3

1

MOV

MOVE
Source

N10:0

Dest

O:1.0

1

I:2.0

] [

0

] [

I:2.0

OSR

B3

2

MOV

MOVE
Source

N10:8

Dest

O:1.0

1

I:2.0

]/[

0

]/[

I:2.0

OSR

B3

3

COP

COPY FILE
Source

#N10:4

Dest

#O:1.0

Length

4

Rung 2.0
If the degrees selector switch is switched to Fahrenheit, configure all four channels to read in
degrees Fahrenheit. The default for channel 0 is to read the ambient temperature thermocouple.

Rung 2.1
If the ambient/cabinet selector switch is switched to ambient, and the degrees selector switch is
switched to Fahrenheit, configure channel 0 to read the ambient temperature thermocouple in
degrees Fahrenheit.

Rung 2.2
If the ambient/cabinet selector switch is switched to cabinet, and the degrees selector switch is
switched to Fahrenheit, configure channel 0 to read the CJC sensor in degrees Fahrenheit.

Rung 2.3
If the degrees selector switch is switched to Celsius, configure all four channels to read in
degrees Celsius. The default for channel 0 is to read the ambient temperature thermocouple.

Degrees Selector
Switch =
Fahrenheit

Degrees Selector
Switch =
Fahrenheit

Degrees Selector
Switch =
Fahrenheit

Ambient/Cabinet
Selector Switch =
Ambient

Ambient/Cabinet
Selector Switch =
Ambient

Degrees Selector
Switch =
Celsius

Configure Channels

Configure Channels

Configure Channels

Configure Channels