Environmental specifications, Input specifications, Environmental specifications input specifications – Rockwell Automation 1746-INT4 Thermocouple/MV Isolated/ User Manual User Manual

Page 80

Advertising
background image

Publication 1746-UM614B-EN-P - September 2007

80 Module Specifications

(1) Refer to the thermocouple manufacturer for the correct extension wire.

Environmental
Specifications

Input Specifications

Max wire size

Two 1.6 mm (14 AWG) wires per terminal

Max cable impedance

150

Ω

max loop impedance, for < 1LSB error

Terminal strip

Removable, catalog number 1746-RT32

Attribute

Value

Attribute

Value

Temperature, operating

0… 60 °C (32…140 °F)

Temperature, storage

-40…85 °C (-40…185 °F)

Relative humidity

5…95% (without condensation)

Agency certification
(when product is marked)

CSA certified

CSA Class I, Division 2, Groups A, B, C, D certified
Hazardous Locations

UL listed

CE marked for all applicable directives

Attribute

Value

Type of input (selectable)

Thermocouple Type C 0…2317 °C

(32…4201 °F)

Thermocouple Type D 0…2317 °C

(32…4201 °F)

Thermocouple Type J -210…760 °C

(-346…1400 °F)

Thermocouple Type K -270…1370 °C

(-454…2498 °F)

Thermocouple Type T -270…400 °C

(-454…752 °F)

Thermocouple Type E -270…1000 °C

(-454…1832 °F)

Thermocouple Type R 0…1768 °C

(32…3214 °F)

Thermocouple Type S 0…1768 °C

(32…3214 °F)

Thermocouple Type B 300…1820 °C

(572…3308 °F)

Thermocouple Type N 0…1300 °C

(32…2372 °F)

1.6 mm (14 AWG)

Millivolt (–50…50 mV dc)
Millivolt (–100…100 mV dc)

Thermocouple linearization

IPTS–68 standard, NBS MN–125, NBS MN–161

Cold junction compensation Accuracy ±1.5 °C (34.7 °F), 0 … 70 °C (32…158 °F)

Input impedance

Greater than 10 M

Ω