Wire the module, Cold-junction compensation (cjc) – Rockwell Automation 1746-INT4 Thermocouple/MV Isolated/ User Manual User Manual

Page 30

Advertising
background image

Publication 1746-UM614B-EN-P - September 2007

30 Install and Wire the Module

Wire the Module

The module contains a green, 18-position, removable terminal block.

Terminal Block

Cold-junction Compensation (CJC)

In case of accidental removal of one or both thermistors, replace them
by connecting them across the CJC terminals located at the top and/or
bottom left side of the terminal block. Always connect the red lug to
the (+) terminal (to CJC A+ or CJC B+).

CJC Connection

ATTENTION

Disconnect power to the SLC controller before attempting to
install, remove, or wire the terminal block.

ATTENTION

Do not remove or loosen the cold-junction compensating
thermistors located on the terminal block. Both thermistors are
critical to be sure of accurate thermocouple input readings at
each channel. The module does not operate in the
thermocouple mode if a thermistor is removed.

CJC A-

CJC A+

CJC B+

CJC B-

n/c

(Terminal Block Spare Part Catalog Number 1746-RT32)

Release Screw

Channel 0+

Channel 0-

Channel 1+

Channel 1-

Channel 2+

Channel 2-

Channel 3+

Channel 3-

Do not connect
to this terminal.

Release Screw

CJC Assembly

CJC Assembly

Do NOT use
these
connections
See page 26.

Always attach
red lug to the
CJC+ terminal.

Bottom of Terminal Block

Thermistor

Advertising