Use channel status words – Rockwell Automation 1746-INT4 Thermocouple/MV Isolated/ User Manual User Manual

Page 53

Advertising
background image

Publication 1746-UM614B-EN-P - September 2007

Channel Configuration, Data, and Status 53

Use Channel Status Words

Channel status words are stored in the SLC controller’s input image
file at addresses I:e.4 to I:e.7 (where e is the slot number assigned to
the module). Status words 4…7 correspond to and reflect the
configuration of channels 0…3 (O:e.0…O:e.3).

Whenever a channel is disabled (O:e.x/11 = 0), its corresponding
status word is zero. This condition tells you that input data contained
in the channel data word is invalid and should be ignored.

The status word of an enabled channel indicates the following status:

Bits 0…10 reflect the channel configuration

Bit 11 indicates whether the channel is enabled or disabled
(configuration)

Bits 12…15 indicate detected faults should they occur

We present status words as they appear in the input image table at
I:e.4…I:e.7.

Module Input Image (Status Words)

IMPORTANT

The status word from a disabled channel is always zero.

CH 0 Channel Status Word

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

CH 1 Channel Status Word

CH 2 Channel Status Word

CH 3 Channel Status Word

O:e.4

O:e.5

O:e.6

O:e.7

Reflect the Configuration Word

1 = detected open input condition
1 = detected under-range input value
1 = detected over-range input value
1 = detected invalid channel configuration