Publication 1746-UM614B-EN-P - September 2007

Quick Start 21

Data Table Display of Integer File N10:0

8. Write ladder logic to process the thermocouple input data for

your application.

9. Apply power, download your program to the SLC processor and

put the controller into Run mode.

In this example, during a normal start up, the module status LED
indicator and channel status 0 LED indicator turn on.

Dest

# O:1.0

Length

1

address

15 data 0 address 15 data 0

N10:0 0000 1000 0000 0000

] [

COP

COPY FILE
Source

# N10:0

First Pass Bit

S:1

15

Ladder Logic to Transfer N10:0 to the Module:

When cycling power, the first pass bit
(S:1/15) is set for one scan, enabling the
COPY instruction to transfer the
configuration word to the processor’s
output image table. From there it is
transferred to the module in the
processor’s I/O scan.

Channel 1 Data Word

Channel 2 Data Word

Channel 3 Data Word

Bit 15

Bit 0

Word 1

Word 2

Word 3



Address

I:1.0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Channel 0 Data Word

Word 0

Word 7

Channel 1 Status Word

Channel 2 Status Word

Channel 3 Status Word

Channel 0 Status Word

(Variable Thermocouple Input Data)

Address

I:1.0
I:1.1
I:1.2
I:1.3

I:1.7









SLC 500 Controller
Data Files

Output Image

Input Image
(8 words)

In this example, the module is located in slot 1.

0

1

2

3

INPUT

MODULE STATUS

THERMOCOUPLE/mV

CHANNEL

STATUS

ISOLATED

Channel LED Indicator

Module Status LED Indicator