Install and Wire the Module 33

7. At the source-end of cables from mV devices:

remove the drain wire and foil shield.

apply shrink wrap as an option.

connect to mV devices keeping the leads short.

Cable Preparation and Connections to Minimize Electrical Noise Interference

IMPORTANT

If noise persists, try grounding the opposite end of the cable,
instead. (Ground one end only.)

Terminal Block

Wires

9.5 mm
(3/8 in.)

Remove drain wire and
foil shield at casing.

Cables

Keep the length of
unshielded wires as
short as possible.

Limit braid length to 304.8 mm
(12 in.) or less. Solder braid to lug
attached to bottom row of I/O
chassis bolts.

9.5 mm (3/8 in.)

9.5 mm (3/8 in.)

Cables

Solder drain
wires to braid
at casings.

Keep the length of
unshielded wires as
short as possible.

Signal
Wires

Connect I/O chassis bolt
to earth ground.

Ungrounded End at Source Device

Grounded End at I/O Chassis