8 - module diagnostics and troubleshooting, Module and channel diagnostics, Chapter 8 – Rockwell Automation 1746-INT4 Thermocouple/MV Isolated/ User Manual User Manual

Page 65: Module diagnostics and troubleshooting, Chapter

Advertising
background image

65

Publication 1746-UM614B-EN-P - September 2007

Chapter

8

Module Diagnostics and Troubleshooting

This chapter describes troubleshooting with channel-status and
module-status LED indicators. It explains the types of conditions that
might cause the module to flag an error, and suggests what corrective
action you could take. Topics include:

module and channel diagnostics.

status indicators.

troubleshooting flowchart.

replacement parts.

contacting Rockwell Automation.

Module and Channel
Diagnostics

The module operates at two levels.

Module level

Channel level

Module level operation includes functions such as cycling power,
configuration, and communication with the SLC processor. ON
indicates the module is OK. OFF indicates a fault.

Channel level operation includes functions such as data conversion
and open-circuit detection. ON indicates the channel is OK. Blinking
indicates a fault.

The module performs internal diagnostics at both levels, and
immediately indicates detected error conditions with either of its status
LED indicators. When a status LED indicator is continuously ON, the
status is OK.

Module Diagnostics When Cycling Power

When you cycle the module’s power, the module performs a series of
internal diagnostic tests. If the module detects a failure, its module
status LED indicator remains off.

Advertising