Data file 6 - control – Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual

Page 104

Advertising
background image

B-8

SLC 500 Data Files and Logical Addressing

Publication 1747-6.1

Data File 6 - Control

These are 3-word elements, used with Bit Shift and Sequencer
instructions. Word 0 is the status word, word 1 indicates the length of
stored data, and word 2 indicates position. This is illustrated below.

Assign control addresses as follows:

Format

Explanation

Rf:e

R

Control

f

File number.

Number 6 is the default file. A file
number between 10-255 can be used if
additional storage is required.

:

Element delimiter

e

Element
number

Ranges from 0 to 255. These are 3-word
elements. See the figure above.

Examples:

R6:2

Element 2, control file 6.

Address bits and words by using the format RF:e.s/b where Rf:e is explained above, and

. is the word delimiter
s indicates subelement
/ is the bit delimiter
b indicates bit

R6:2/15
R6:2/13
R6:2/11
R6:2/10

R6:2/9
R6:2/8

R6:2.1
R6:2.2

R6:2.1/0
R6:2.2/0

Enable bit
Done bit
Error bit
Unload bit
Inhibit bit
Found bit

Length value
Position value

Bit 0 of the length value
Bit 0 of the position value

EN

14

DN

12

ER UL IN FD

7

6

5

Internal Use

15

13

11 10 9

Length of Bit array or File

8

Bit Pointer or Position

4

0

0

1

2

Word

3

2

1

Control Element

Addressable Bits

Addressable Words

o
rror

od o

od

oo

d r

r o ddr