6 - quick recall functions, Quick recall function overview, Defining quick recall functions – Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual

Page 51: Quick recall functions, Chapter

Advertising
background image

Publication 1747-6.1

Chapter

6

Quick Recall Functions

This chapter describes how to:

• define Quick Recall Functions

• use Quick Recall Functions

• clear Quick Recall Functions

Quick Recall Function
Overview

The module has the capability to let you define and use up to 10 data
file address Quick Recall Functions. These functions are stored in the
module’s nonvolatile memory. They allow you to assign frequently
accessed data file addresses to a simplified keystroke procedure. You
may later recall these addresses by pressing two keys instead of using
the addressing procedure described in the previous chapter.

Quick Recall Functions also provide the ability to write data to
selected data file addresses when the module is configured for the
Monitor mode. This Monitor Override feature is enabled in the
Module Setup Procedure described in chapter 3.

Defining Quick Recall
Functions

The available Quick Recall Functions are numbered F(0) through
F(9). For example, to assign address T4:1.ACC to Quick Recall
Function F(1):

1. Configure the module for the Modify mode.

2. Make sure the module is attached to a processor.

3. Enter the data file address:

Press

>6+,)7@ >7@ >@ >$&&@ >(17(5@

4. The address and its current value are displayed:

5. To define Quick Recall Function F(1):

Press

>6+,)7@ >) @ >) @ >@ >(17(5@

6. The Quick Recall Function for that address is now stored in the

module nonvolatile memory. The display shows the following
for three seconds:

T4:1.ACC

9999

Macro 1 Defined

T4:1.ACC

Advertising