N10:2, B3:1.0/3 – Rockwell Automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTAM) User Manual

Page 75

Advertising
background image

Message Capability

8-15

Publication 1747-6.1

7-word message control block: N7:30 through N7:36

N7:30 = 0

message status

N7:31 = 2

DTAM node address

N7:32 = 18

message length

N7:33 = 100

offset (overwrite capability)

N7:34 through N7:36 = unused

18-word local source file: N7:40 through N7:57

N7:40 through N7:47

8-word message text

N7:48 through N7:51

data entry destination address

In this example the data entry destination address is N10:2. Memory
locations N7:48 through N7:51 are assigned as follows:

N7:52 = 250

initial value word

N7:53 through N7:57

acknowledge bit address

In this example the acknowledge bit address is B3:1.0/3. Memory
locations N7:53 through N7:57 are assigned as follows:

The following example is for the 8-word message in rung 2:

N10:2

File Type

File Number

Element

N7:48=7

N7:49=10

N7:50=2

Important:

N10:2 must be allocated. See your software user
manual. Otherwise the DTAM displays

,OOHJDO

&RPPDQG

.

B3:1.0/3

File Type

File

Number

Element

N7:53=3

N7:54=3

N7:56=0

Subelement

Bit

N7:57=3

N7:55=1

Read/Write:
Target Device:
Control Block:
Local Source File Address:
Target Node:
Target Offset:
Message Length in elements:

WRITE

485 CIF

N7:60
N7:70

2

100

8

ignore if timed out:

to be retried:

awaiting execution:

error:

message done:

message transmitting:

TO

NR

EW

ER

DN

ST

0
0
0
0
0
0
0

Advertising