TROUBLESHOOTING CONSIDERATIONS

GENERAL ERROR SCREEN

COMM LED

PROBABLE CAUSES

RECOMMENDED ACTION

XX is inactive

1

LED illuminated green or
flashing green

The processor at that node
address is not powered up

Power up the processor.

The processor at that node
address is disconnected from
the network

Activate that processor on the
network.

A fault has caused that
processor node addressto
change to a default of one

Change the processor node
address.

The processor is set at the
wrong baud rate

Change the processor baud
rate.

XX is not a CPU

a

LED illuminated green or
flashing green

The node addressyou are
attempting to attach to is a
programming device or
another DTAM

Abort.

A programming device has
been connected to the network
with the same node address
as a processor

Change the node address of
the programming device.

XX not supported

a

LED illuminated green or
flashing green

The node addressyou are
attempting to attach to is a non-
supported device

Abort.

Contact your local Allen-
Bradley sales office.

1. Where XX is the Node Address Value.